Connection Kit for frost protection
Our Single Cool with frost protection pipes are equipped with a self-regulating 10 W/m heating cable to prevent stagnant water from freezing.
The heating cable is AC powered, and must be connected to a 220 VAC/50-60 hertz line to operate. The power line requires over-current protection through a 16A 30mA RCD (residual-current device). To prevent the 10 W/m heating cable from dissipating energy when surrounding temperatures are well above the freezing point, the use of an ambient thermostat to automatically interrupt the power supply at a pre-set temperature (e.g. 2°C) is recommended.
The total length of the heating cable should not exceed 100 m. Where longer heating cables are required, separate power supplies should be foreseen, each feeding maximum 100 m cable.
The heating cable can be cut to any desired length (< 100 m and as a function of the pipe length). To assure proper functioning of the cable, and to prevent possible short circuits, the cables’ two conductive wires should be electrically insulated from each other.
![HCBOX – Electrical junction box](https://www.keaneenvironmental.ie/wp-content/uploads/2015/10/HCBOX-boite-jonction.jpg)
![HCSL – Electrical connection and insulation kit](https://www.keaneenvironmental.ie/wp-content/uploads/2015/10/HCSL-electrical-connection-and-insulation-kit.jpg)
![HC-THERM Ambient Thermostat](https://www.keaneenvironmental.ie/wp-content/uploads/2015/10/Product-40_kl-210x300-e1445424337750.jpg)